R-410A is a binary blend of HFC-32 and HFC-125. It has no chlorine content, no ozone depletion potential, and only a modest global warming potential. R-410A is the leading substitute for R-22 in residential and light commercial air-conditioning and heat pump systems. It exhibits higher pressure and refrigeration capacity than R-22 and should be used only in systems specially designed for R-410A. R-410A will require the use of POE lubricants.
Physical Properties
| Molecular Weight |
72.58 |
| Boiling Point at 1 atm (101.3 kPa) |
-52.7°C |
| Critical Temperature |
72.5°C |
| Critical Pressure |
4964.2 kPa |
| Critical Density |
0.500 g/cm3 |
| Liquid Density at 30°C |
1038.2 kg/m3 |
| Liquid Heat Capacity at 30°C |
1.78 kJ/(kg·°C) |
Vapor Heat Capacity at Constant Pressure at 30°C and 1 atm (101.3 kPa) |
0.85 kJ/(kg·°C) |
| Heat of Vaporization at Boiling Point |
256.7 kJ/kg |
| ODP |
0 |
| GWP |
0.29 |
Packaging and Storage
R-410A is available in disposable steel cylinders (11.3kg/30lb), returnable steel cylinders (800kg/926L). The filling ratio is not more than 0.87kg/L. Cylinders should be stored in cool, dry and well-ventilated area away from sunlight and rain.
|
|
|
|
| |
|
|
|